Smoke Extract Fans 400 ºC/2h - 300 ºC/2h

CJLINE/EC

CJLINE/EC

Air extract units with linear inlet and outlet, equipped with EC Technology IE5 motor

Air extraction units with linear inlet and outlet, equipped with EC Technology IE5 motor with integrated electronics.

Fan:
• Galvanised sheet steel structure.
• Backward curved impeller made of sheet steel.
• Linear airflow direction.

Motor:
• High efficiency EC Technology motors with integrated electronics, regulated by 0-10 V or 4-20 mA.
• IE5 efficiency motors, class F and IP55 protection.
• Single-phase 220-277 V 50/60 Hz.
• Working temperature: -25 ºC +60 ºC.

EC CONTROL:
Supplied as an optional accessory. Control panel for ventilation systems with EC Technology motors with the electronics integrated in the motor itself. With the following characteristics:
• CPC: Constant pressure control.
• CFC: Constant flow control.
• DAY/NIGHT: Double pressure setpoint adjustment according to time of day.
• External sensor: Compatible with temperature, humidity, air quality or CO sensor.
• Equipment preconfigured in constant pressure mode with 100 Pa set point.

Finish:
• Galvanised steel sheet.
Products
Price search
Price finder
1. Enter the model or
a product code:
    2. Price of the product
    (without VAT):

    PVP: _.___,__ €